Nominal operating voltage 3×380 VAC to 415 VAC ±10%
Overload capability 1.6×rated current for 1 minute, once per hour
Operating frequency 50Hz ±1Hz
Total harmonic current distortion THDi* ≤10% at rated power
Total demand distortion TDD According to IEEE 519
Nominal motor drive input power rating 1.5 to 710 kW
High potential test voltage P –> E 2160 VAC (1 s)
Earthing system TN, TT, IT
Efficiency >98% for rated voltage and power
Overvoltage category OV III (IEC 60664-1 / UL 61800-5-1)
Cooling Internal fan cooling or external cooling***
Temperature range (operation and storage) –25°C to +45°C fully operational +45°C to +70°C derated operation**** –25°C to +85°C transport and storage
Cooling Internal fan cooling or external cooling***
Protection category IP 00, IP 20
Flammability corresponding to UL 94 V-2
Design corresponding to Filter: UL 61800-5-1, EN 61800-5-1, Chokes: EN 61558-2-20 or EN 60076-6
SCCR** 100 kA
MTBF (Mil-HB-217F) >200,000 h @ 45°C/400V
* System requirements: THDv <2%, line voltage unbalance <1%
Note: performance specifications in this datasheet refer to six-pulse diode rectifiers.
SCR rectifier front-end will produce different results, depending upon the firing angle of the thyristors.
THDi ≤10% at rated power for filter<6kW/HP
** External UL-rated fuses required. Please consult the user manual.
*** Please check the inlet air flow required for cooling table further in this document and the user manual.
**** Iderated = Inominal*SQRT((Tmax-Tamb)/(Tmax-Tnominal)) =Inominal*SQRT((70°C-Tamb)/25°C)