JDT10

Protect AC motors from destructive effect of peak voltages

Product Overview

Downloads

JDT10

• Reduction of drive output voltage dv/dt • Reduction of voltage stress at motor windings • Protect AC motors from destructive effect of peak voltages • Increase of motor service life • Improvement of system reliability

Key words:

JDT10

Classification:

Product Description

Maximum continuous operating voltage 3×550 VAC

Nominal operating voltage 3x500 VAC

Max. peak voltage ≤1000 V

Rated currents 14 to 1200 A @ 40°C

Overload capability 1.5 × rated current for 1 minute, ones per hour

Typical dv/dt reduction Factor 8 to 12

Voltage drop <3 V @ 50 Hz

Motor frequency 0...60 Hz (with derating up to 120 Hz, see graph)

Motor cable length Up to 500 m (see graph page 2)

Switching frequency max. 16 kHz, depending on motor cable length and operating voltage (see graph)

High potential test voltage P -> E 3300 VAC, 1 minute P -> P 3300 VAC (wihtout caps), 1 minute P -> P 2500 VDC caps, 2 s

Overvoltage category OV III (IEC 60664-1)

Temperature range (operation and storage) -25°C to +40°C fully operational +40°C to +100°C with derating -25°C to +100°C transport and storage

Protection category IP 00

Flammability corresponding to UL 94 V-2

Design corresponding to UL 61800-5-1, EN 61800-5-1, EN 61558-2-20 or EN 60076-6

Get Product Inquiry